Product Description
Δ STANDARD CONFIGURATION
1) Powered by original PERKINS water-cooled diesel engine.
2) PERKINS diesel engine with 12 months global warranty.
3) Original STAMFORD | LEROY SOMER | GENLITEC Single bearing alternator with insulation class H and IP23.
4) Standard CHINT or DELIXI circuit breaker, ABB as an optional.
5) Steel base fuel tank with anti-vibration mounting.
6) Based at leaset 8 hours build-in fuel tank ensure daily use.
7) Industrial 9 dB muffler exhaust system, free-maintenance battery, complete set of user's manual.
8) Flexible fuel lines and lube oil, water & fuel drain cocks.
9) Standard SMARTGEN HGM6120N antomatic start digital controller.
10) Standard Shrink wrap packing method (Plywood packing box as optional).
Δ TESTING ITEMS
GENLITEC POWER provides a full line of brand new and high quality products.
Each and every unit is strictly factory tested before shipment.
1) Parts faults testing
2) Fuel tank pressure testing
3) Bolt tightening torque testing
4) Painting thickness testing
5) Voltage bearing and insulation testing
6) Noise testing
7) Loading Testing: 25%, 50%, 75%, 100%, 110% load to check verify that all control systems, alarm and shut-down protection.
Δ OPTIONAL SUPPLY
1) Weatherproof canopy / Soundproof canopy / Trailer-mounted
2) Engine / Alternator Pre-heaters
3) Auto load sharing & synchronization panel
4) Build-in ATS (Auto start & stop Main Failure (AMF)
5) Large 12/24 hours fuel tank
6) Power output sockets
Δ SPECIFICATION
GENSET MODEL | GPC125S5 |
Prime power | 100KW/125KVA |
Standby power | 110KW/138KVA |
Rated Voltage | 400/230V |
Rated frequency | 50Hz |
Rated Speed | 1500rpm |
Power Factor | 0.8(lagging) |
Dimensions (L×W×H) | 2160×820×1300mm |
Net Weight | 1200KG |
DIESEL ENGINE SPECIFICATION | |
Engine model | CUMMINS 6BTAA5.9-G2 |
Number of Cylinders | 6 |
Cylinder arrangement | Vertical in-line |
Cycle | Four stroke |
Aspiration | Turbocharged after air-air cooled |
Bore×Stroke (mm×mm) | 102 x 120 |
Displacement (Liter) | 5.9 |
Compression Ratio | 17.5:1 |
Speed Governor | Electrical |
Cooling System | Water cooled |
Speed Stability (%) | ≤1% |
Total lubrication system capacity (L) | 16.4 |
Fuel Consumption at 100% Load (L/h) | 211 |
Starting Method | DC24V Electrical starting |
ALTERNATOR SPECIFICATION | |
Alternator model | STAMFORD UCI274ES |
Number of Phase | 3 |
Connecting Type | 3 Phase and 4 Wires |
Number of Bearing | 1 |
Protection Grade | IP21 |
Altitude | ≤1000m |
Insulation Class | H |
Telephone Influence Factor (TIF) | ≤50 |
THF | ≤2% |
Voltage Regulation, Steady State | ≤±1% |
Transient State Voltage | ≤-15%~+20% |